SPY CENTER 24 PLUS
- Supply and control system at safety extra-low voltage (SELV) for installations with LED luminaires with centralized supply at 24 Vdc
- Equipped with new Lithium Iron Phosphate batteries capable of delivering up to 40% more power
Lista de resultados, divididos por función
It allows to control every single luminaire in each circuit.
ADVANTAGES
- Equipped with new Lithium Iron Phosphate batteries capable of delivering up to 40% more power.
- Up to 72 W per single circuit (+20% compared to Spy Center 24)
- Complete programming flexibility for functioning type: M (Maintained) and N/M (Non Maintained) via configuration software
- Possibility to configure each luminaire of each circuit, independently, as M (Maintained) N/M (Non Maintained)
- Every single device can be turned on/off or dimmed remotely
- It allows to program each single luminaire in local emergency mode (built-in detection of local black out is available on the predisposed luminaires)
- Automatic luminaire acquisition
- User friendly multilingual interface
- Possibility of communication through integrated MODBUS protocol
- Log book: periodic controls register for quick viewing of the event log
- The functionality and duration tests are freely programmable
LINERGY CLOUD
The web platform for configuring and controlling emergency installations based on Linergy centralized systems.
Spy Center 24 Plus come with Linergy Cloud.
TECHNICAL FEATURES
- Lithium Iron Phosphate (LiFePO4) batteries
- Input supply voltage: mono-phase 230 Vac
- Output supply voltage: 24 Vdc
- The Powerline Communication technology for each circuit make the installation easy and flexible: electrical power and communication bus are shared over the same cables
- Central unit with touchscreen color display
- Maximum overall load capacity: 8 circuits, 160 luminaires
- Maximum load for each circuit: 60 W, 20 luminaires
- Lines short-circuit protected
- 4 inputs at 230 Vac, 8 inputs for clean contact
- 8 relay outputs (NO/NC) for installation status signalling
- Ethernet port with TCP/IP protocol for intranet/internet connection
- Integrated web server for remote configuration and control via generic web browser
- System compliant to European norms: EN 50171, EN 62485-2, EN 62034
- Time intervals between verification tests comply to European norms: EN 50172, UNI 11222
SYSTEM COMPOSITION
The Spy Center 24 Plus central unit must be used in conjunction with luminaires of the Spy Center 24 family.
The central unit can monitor and control each luminaire.
Spy Center 24 Plus can only be used in conjunction with Linergy emergency luminaires of the Spy Center 24 family. It's not possible to drive ordinary lighting devices.
POWER AND CABLE SECTION
Power capacity | Cable section 1,5 mm2 | Cable section 2,5 mm2 |
72 W | 50 m | 80 m |
60 W | 60 m | 100 m |
50 W |
70 m
|
120 m |
40 W | 90 m | 150 m |
30 W | 120 m | 200 m |
20 W | 180 m | 300 m |
10 W | 360 m | 560 m |
The maximum voltage drop at full load must not exceed 4V